Economite EC200 & EC300
Space saving design, rock solid, packed with power all rolled into one great burner!
The standard Economite EC Series Power Gas Burners are engineered to match a wide variety of applications or customized to meet OEM applications. The compact design not only meets or exceeds industry standards; it also packs a lot of power for its size. Each unit is fully assembled and factory fire tested assuring you a high quality performance product. Installation is effortless with our integrated junction box and universal mounting flange.
Specialized Features
Adjustable External Air Shutter with Indication
- Visual indication of air shutter position
- Faster burner set up
Pre-Piped, Pre-Wired, Factory Fired Tested
- Ease of Installation
- Reliable operational sequence
Compact Design and Small Footprint
- Lightweight for lower shipping cost
- Space saving compatibility to different applications firing into small combustion chambers
- Light and compact removable burner assembly from the burner tube and flange
Interchangeable Stainless Steel Burner Retention Heads
- Compatibility to different applications
- Operates under variable draft pressure conditions
- Firing into small combustion chambers
Integrated Direct Spark Ignition System with Pre-Purge
- Compliance with ANSI Z21.20 standard
- Timed pre-purge clears the combustion chamber before ignition cycle
- Proper sequencing of the burner operation
Air Shutter Positive Lock Fitting
- No shifting of air shutter caused by vibration
- Reduction of unauthorized adjustment
Universal Mounting Flange
- Application flexibility
- Universal Bolt Pattern
- OEM welded flange available
Field Convertible Triple Function Redundant Gas Valve
- Quiet and maintenance-free
Space Saving Design
Rock Solid
Packed with Power
All Rolled into One Great Burner!
A
|
B
|
C
|
D
|
E
|
F
|
G**
|
H
|
|
EC200 |
5 5/16“
|
3 11/16“
|
7 1/2“
|
8 5/8“
|
7 1/2“
|
Ø 4″
|
6 13/16“
|
6 13/16“
|
EC300 |
6 9/16“
|
3 11/16“
|
8 1/4“
|
8 5/8“
|
7 1/2“
|
Ø 4″
|
6 13/16“
|
9″
|
**approximate
Model Number: EC200
Minimum Input Rating: 70,000 BTU/hr
Maximum Input Rating: 200,00 BTU/hr
Gas Connection Pipe Size: 3/4″ NPT
Gas Pressure Required Natural or Propane: 6.0″ to 14.0″ W.C.
Nozzle Diameter: 4.0″
Maximum Nozzle Insertion Depth: 6.0″
Motor HP: 1/22
Design Certifications or Listed by: U.L/C.U.L. Listed
Primary Safety Voltage: 24V
Shipping Weight: 25lb
Model Number: EC300
Minimum Input Rating: 90,000 BTU/hr
Maximum Input Rating: 300,00 BTU/hr
Gas Connection Pipe Size: 3/4″ NPT
Gas Pressure Required Natural or Propane: 6.0″ to 14.0″ W.C.
Nozzle Diameter: 4.0″
Maximum Nozzle Insertion Depth: 6.0″
Motor HP: 1/12
Design Certifications or Listed by: U.L/C.U.L. Listed
Primary Safety Voltage: 24V
Shipping Weight: 25lb
Product Information
Installation Manual & Parts List